Description
Highlight
- The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
- Whether you work on motors, generators, cables, or switch gear, the Fluke 1587/1577 Insulation Multimeters are ideally suited to help you with your tasks and at a cost that is far less than buying the two products.
Fluke 1577 Digital Insulation Multimeter
The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
Whether you work on motors, generators, cables, or switch gear, the Fluke 1587/1577 Insulation Multimeters are ideally suited to help you with your tasks and at a cost that is far less than buying the two products.
Features and benefits of the Fluke 1577
Feature
|
1587
|
1577
|
Insulation test voltages 50V, 100V, 250V, 500V, 1000V
|
•
|
|
Insulation test voltages 500V, 1000V
|
|
•
|
Insulation test: 0.01 MΩ to 2.0 GΩ
|
•
|
|
Insulation test: 0.1 MΩ to 600 MΩ
|
|
•
|
Auto discharge of capacitive voltage
|
•
|
•
|
Insulation test smoothing reading
|
•
|
|
Frequency
|
•
|
|
Capacitance
|
•
|
|
Diode test
|
•
|
|
Temperature
|
•
|
|
Min/Max
|
•
|
|
Low pass filter (for work on VSD's)
|
•
|
|
AC/DC Voltage
|
•
|
•
|
DC millivolts
|
•
|
•
|
AC/DC milliamps
|
•
|
•
|
Resistance (0.1 Ω to 50 MΩ)
|
•
|
•
|
Continuity
|
•
|
•
|
Three-year warranty
|
•
|
•
|
Remote probe, test leads, alligator clips
|
•
|
•
|
K-type thermocouple
|
•
|
|
Rugged, utility hard case
|
•
|
•
|
Auto power off to save battery power
|
•
|
•
|
True-rms
|
•
|
•
|
Large display with backlight
|
•
|
•
|
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
|
•
|
•
|
CAT III 1000V, CAT IV 600V measurement category
|
•
|
•
|
Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work
|
•
|
•
|
|
|
|
|
|
Specifications
|
Voltage DC
|
Maximum Voltage:
|
1000 V
|
Accuracy:
|
1577: ±(0.2%+2)
|
|
1587: ±(0.09%+2)
|
Maximum Resolution:
|
0.001V
|
|
Voltage AC
|
Maximum Voltage:
|
1000 V
|
Accuracy:
|
1577: ±(2%+3)
|
|
1587: ±(2%+3)
|
AC Bandwidth:
|
1587: 5kHz*
|
|
*with low pass filter; 3db @ 800 Hz
|
Maximum Resolution:
|
0.1 mV
|
|
Current DC
|
Maximum Amps:
|
400mA
|
Amps Accuracy:
|
1577: ±(1.0%+2)
|
|
1587: ±(0.2%+2)
|
Maximum Resolution:
|
0.01 mA
|
|
Current AC
|
Maximum Amps:
|
400mA
|
Amps Accuracy:
|
1577: ±(2.0%+2)*
|
|
1587: ±(1.5%+2)*
|
|
* 1kHz bandwidth
|
Maximum Resolution:
|
0.01 mA
|
|
Resistance
|
Maximum Resistance:
|
50 MΩ
|
Accuracy:
|
1577: ±(1.2%+2)
|
|
1587: ±(0.9%+2)
|
Maximum Resolution:
|
0.1Ω
|
|
Capacitance(1587 only)
|
Maximum Capacitance:
|
9,999 µF
|
Accuracy:
|
±(1.2%+2)
|
Maximum Resolution:
|
1 nF
|
|
Frequency (1587 only)
|
Maximum Frequency:
|
100 kHz
|
Accuracy:
|
±(0.1%+1)
|
Maximum Resolution:
|
0.01 Hz
|
|
Temperature Measurement (1587 only)
|
|
-40.0 °C to 537 °C
|
|
-40.0 °F to 998 °F
|
|
excluding probe
|
|
Diode Test (1587 only)
|
Range:
|
6 V
|
Resolution:
|
1 mV
|
Accuracy:
|
±(2 % + 1)
|
|
Insulation Test
|
Minimum Test Current @ 1kΩ/V:
|
|
Test Voltages:
|
1577:
|
500, 1000 V
|
1587:
|
50, 100, 250, 500, 1000 V
|
|
Maximum Resistance per Test Voltage:
|
50V:
|
|
100V:
|
|
250V:
|
|
500V:
|
|
1000V:
|
1577: 600 MΩ
|
|
1587: 2 GΩ
|
|
Maximum Resolution per Test Voltage:
|
50V:
|
0.01 MΩ
|
100V:
|
0.01 MΩ
|
250V:
|
0.1 MΩ
|
500V:
|
0.1 MΩ
|
1000V:
|
0.1 MΩ
|
|
Accuracy per Test Voltage:
|
50V:
|
±(3 % + 5)
|
100V:
|
±(3 % + 5)
|
250V:
|
±(1.5 % + 5)
|
500V:
|
1577: ±(2.0 % + 5)
|
|
1587: ±(1.5 % + 5)
|
1000V:
|
1577: ±(2.0 % + 5)
|
|
1587: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ
|
|
Environmental Specifications
|
Operating temperature
|
|
Storage temperature
|
|
|
|
|